FDS-3G

Rectangular Fire Damper FDS-3G

Art. no.: A-FDS-3G

Description

Fire dampers represent passive fire protection, designed with the help of compartmentalization to prevent the spread of toxic gases, smoke and fire. Standard fire dampers are designed and certified in accordance with EN 15650 and tested for EIS criteria according to EN 1366–2. Fire damper together with its installation form an inseparable part of fire resistivity rating. FDS-3G, FDS-EI90S and FDS-EI120S fire dampers are designed for the installations listed and described in their Handbook. By default, all fire dampers are supplied with a manual mechanism or actuator mechanism, optionally with a supply and communication unit. The activation mechanisms are removable and are interchangeable, for example an actuator operated mechanism instead of a manually operated mechanism.

Highlights

• Lightweight construction

• Casing tightness class C as standard

• Exceptionally low pressure drop

• Changeable mechanism

• Two inspection openings for all sizes greater than 200x200 mm

• Great variety of installations rated up to EI120S

• Multiple FDS-EI90S damper installation - up to 4 dampers with a maximum size of 3260 × 2060 mm

• Modulated actuator suitable for system balancing - possibility to open the blade at the desired angle.

Product Types

• FDS-3G

Rectangular fire damper with a maximum fire resistivity of 120 minutes and a single body design. Size range from 100x100 up to 1200x800 mm.

• FDS-EI90S

Rectangular fire damper with a maximum fire resistivity of 90 minutes. Construction of two sheet metal bodies, conductively connected through a calcium-silicate frame. Width greater than 1200 mm and/or Height greater than 800 mm up to maximum size 1600x1000 mm.

• FDS-EI120S

Rectangular fire damper with a maximum fire resistivity of 120 minutes. Construction of two sheet metal bodies, conductively connected through a calcium-silicate frame. Width greater than 1200 mm and/or Height greater than 800 mm up to maximum size 1600x1000 mm.

Activation TypesManually Operated Fire Dampers

By default, all manually operated fire dampers are supplied with manual control, optionally with micro switches and electromagnets. In case of fire, the fire damper is closed automatically. Depending on the version, the damper closes either after the melting of the thermal fuse or by means of remote activation through an electromagnet in impulse connection. After the closing of the damper blade, it is mechanically locked in the closed position and can only be opened manually. The actuating mechanism is activated when the temperature of the air in the duct reaches 74°C and the damper closes within 10 seconds after the melting of the fuse.

• H0

Fire damper with an activation mechanism with a cover, manual crank and with a spring return release mechanism activated by a fusible thermal link set to 74°C (on-demand 100°C).

• H2

Fire damper with an activation mechanism H0 + open and closed indication with 230V AC or 24V AC/DC contact switches.

• H5-2

Fire damper with an activation mechanism H0 + a 24V AC/DC electromagnetic release mechanism in the impulse connection (release takes place when the electromagnet is activated) + open and closed indication with 230V AC or 24V AC/DC contact switches.

• H6-2

Fire damper with an activation mechanism H0 + a 230V AC electromagnetic release mechanism in the impulse connection (release takes place when the electromagnet is activated) + open and closed indication with 230V AC or 24V AC/DC contact switches.

Actuator- Operated Fire Dampers

By default, all actuator operated fire dampers are supplied with an actuator with micro switches, optionally with a power and communication unit. A fire damper can be equipped with a spring return actuator can be closed with command from the building management system, or after the breaching of the thermoelectric fuse. Actuator operated fire dampers are standardly equipped with a thermoelectric fuse, that activates the closing of the damper after the reaching or exceeding of the ambient temperature of 72°C. The actuator power circuit is interrupted and its spring closes the damper blade within 20 seconds.

Belimo actuator available with on demand fuse 95 °C or 120 °C.

• B230T or G230T

Fire damper with an activation mechanism with a Belimo or Gruner spring return actuator (230V AC) with electro-thermal fuse 72°C and auxiliary switches.

• B24T or G24T

Fire damper with an activation mechanism with a Belimo or Gruner spring return actuator (24V AC/DC) with electro-thermal fuse 72°C and auxiliary switches.

• B24T-W or G24T-W

Fire damper with an activation mechanism with a Belimo or Gruner spring return actuator (24V AC/DC) with an electro-thermal fuse 72°C and auxiliary switches, with provided cable connectors for the supply and communication unit (communication unit not part of the mechanism).

• B24T-SR or G24T-SR

Fire damper with an activation mechanism with a Belimo or Gruner spring return actuator (24V AC/DC) with electro-thermal fuse 72°C and auxiliary switches for Modulated dampers (possibility to open the blade at the desired angle). For fire dampers in the size H ≥ 160 mm. Not available for FDS-EI90S/EI120S.

• BST0 or GST0

Fire damper with an activation mechanism with a Belimo (BST0) or Gruner (GST0) spring return actuator (AC/DC 24 V) with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply unit BKN230-24 (supply through unit: AC 230 V, communication: 2-wire to BKS...) or Gruner supply and communication unit FSC-UFC24-2 (supply through unit: AC 24 V, communication: Modbus/BACnet).

• BST1

Fire damper with an activation mechanism with a Belimo spring return actuator (AC/DC 24 V) with an electro-thermal fuse 72°C and auxiliary switches, with a supply and communication unit (SLC powered) BC24-G2 (THC).

• BST2

Fire damper with an activation mechanism with a Belimo spring return actuator (AC/DC 24 V) with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication unit (AC 230 V) BKN230-24-MOD (Modbus/BACnet).

• BST3

Fire damper with an activation mechanism with a Belimo spring return actuator (AC/DC 24 V) with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication unit (AC 230 V) BKN230-24-C-MP (SBS/MP).

• BST10

Fire damper with an activation mechanism with a Belimo spring return actuator (AC/DC 24 V) with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication unit (AC 230 V) BKN230-24-PL (Powerline).

Other communication units are possible on demand.

Design

Fire dampers have casings made from galvanized sheet metal. Blades from non-asbestos insulants have a rubber seal for cold smoke and an intumescent seal, that expands in a fire situation.

Material Composition

The product contains galvanized sheet metal, calcium silicate board, fireproof carbon fiberglass, polyurethane foam and ethylene-propylene rubber. These are processed in accordance with local regulations. The product contains no hazardous substances, except for the solder in the thermofuse, which contains a milligram of lead.

List of Accessories

Detailed information about accessories for FDS-3G, FDS-EI90S and FDS-EI120S is available in SystemairDESIGN under Fire Damper Accessories.

• AM-FD: Activation Mechanisms

• CBS-FD: Cover Boards

• IPOS-FD: Insulation Cover Plates

• IKOWS-FD: Installation Kit for Installation on a Wall and out of a Wall Using Promatect Boards

Technical parameters

Dimensions and weights
Weight 1 kg
AM-FD - Systemair
Art. no.: A-AM-FD
AM-FD

Activation Mechanism for FD dampers

.
CBS-FD - Systemair
Art. no.: A-CBS-FD
CBS-FD

Cover Boards, Square for FD

.
DES-FD - Systemair
Art. no.: A-DES-FD
DES-FD

FDS extension adapter

.
FCS - Systemair
Art. no.: A-FCS
FCS

Flexible dilatation Compensator, Square

.
IKOWS-FD - Systemair
Art. no.: A-IKOWS-FD
IKOWS-FD

Installation Kit for Out/on the Wall using boards, Square

.
IPOS-FD - Systemair
Art. no.: A-IPOS-FD
IPOS-FD

Installation Plates for Out/on the Wall using Wool, Square

.
LEAS - Systemair
Art. no.: A-LEAS
LEAS

Damper Extension by Thick-wall instalation

.
Multi-Belt-FD-2480x80x0,9 - Systemair
Art. no.: A-MT-BELT-FD
Multi-Belt-FD-2480x80x0,9

Sheet metal Belt for MULTI inst.FDS-EI90S incl.screws

.
SSAS - Systemair
Art. no.: A-SSAS
SSAS

Adapter with a Smoke Sensor

.