Acest produs nu se mai fabrică

CWK 160-3-2,5 Duct cooler,circ

Cod produs: 30022

CWK water-cooling battery for circular ducts

Casing of galvanised sheet steel with copper tubes and aluminium fins. Inspection covers for easy cleaning and maintenance. 

Connection sleeves with rubber seal.

Max operating temperature 150 °C

Max operating pressure 1,6 MPa (16Bar)

Parametri tehnici

Dimensiuni și greutăți
Dimensiune tubulatură; Circular, intrare 160 mm
Dimensiune tubulatură; Circular, ieșire 160 mm
Greutate 6,2 kg
Altele
Tip conexiune tubulatură Circular
Water temp 6/12° C
Air Air Air Air Air Air Capacity Water Water

flow

velocity

pressure

before

before

after

flow

pressure

drop

drop

CWK

(m3/h)

(m/s)

(Pa)

(˚C)

(% RH)

(˚C)

(kW)

(l/s)

(kPa)

100-3-2.5 54 2 7 25 50 14.3 0.2 0.01 < 0.5

54

2

7

30

45

15.8

0.4

0.01

1

100

3.5

22

25

50

16.4

0.3

0.01

1

100

3.5

22

30

45

18.5

0.5

0.02

2

145

5

58

25

50

17.5

0.4

0.02

1

145

5

58

30

45

20

0.6

0.02

3

125-3-2.5

85

2

3

25

50

12.6

0.5

0.02

3

85

2

3

30

45

13.5

0.7

0.03

5

150

3

9

25

50

14.5

0.7

0.03

5

150

3

9

30

45

15.7

1.1

0.04

10

215

4.5

18

25

50

15.6

0.8

0.03

7

215

4.5

18

30

45

17.0

1.4

0.05

16

160-3-2.5

145

2

9

25

50

14.4

0.7

0.03

4

145

2

9

30

45

15.6

1.0

0.04

10

250

3.5

24

25

50

16.1

0.9

0.04

8

250

3.5

24

30

45

17.4

1.5

0.06

20

355

5

45

25

50

17.0

1.1

0.04

11

355

5

45

30

45

18.4

1.3

0.08

32

200-3-2.5

225

2

6

25

50

14.1

1.0

0.05

2

225

2

6

30

45

15.3

1.6

0.06

5

390

3.5

17

25

50

15.9

1.4

0,06

4

390

3.5

17

30

45

17.3

2.3

0.09

9

555

5

33

25

50

16.9

1.7

0.07

5

555

5

33

30

45

18.4

3.1

0.12

15

250-3-2.5

360

2

6

25

50

14.2

1.6

0.06

2

360

2

6

30

45

15.4

2.5

0.10

5

630

3.5

18

25

50

16.0

2.2

0.09

4

630

3.5

18

30

45

17.3

3.8

0.15

10

900

5

34

25

50

17.0

2.7

0.11

6

900

5

34

30

45

18.2

5.1

0.20

17

315-3-2.5

560

2

7

25

50

14.5

2.4

0.10

3

560

2

7

30

45

15.4

3.9

0.16

7

985

3.5

20

25

50

16.1

3.4

0.13

5

985

3.5

20

30

45

17.2

6.1

0.24

14

1410

5

39

25

50

17.0

4.3

0.17

8

1410

5

39

30

45

18.1

8.3

0.33

25

400-3-2.5

900

2

9

25

50

15.2

3.4

0.14

2

900

2

9

30

45

16.3

5.8

0.23

5

1590

3.5

25

25

50

16.8

4.8

0.19

4

1590

3.5

25

30

45

17.8

9.3

0.37

12

2280

5

49

25

50

17.6

6.1

0.24

6

2280

5

49

30

45

18.6

12.8

0.51

22

øD

B

H

ødy

F

G

K

L

kg

CWK 100-3-2,5

100

251

180

10

100

40

276

356

4,4

CWK 125-3-2,5

125

326

255

10

175

40

276

356

6,5

CWK 160-3-2,5

160

326

255

10

175

40

276

356

6,7

CWK 200-3-2,5

200

411

330

22

250

40

276

356

9,4

CWK 250-3-2,5

250

486

405

22

325

40

276

356

11

CWK 315-3-2,5

315

560

504

22

400

40

276

356

14,3

CWK 400-3-2,5

400

710

529

22

425

65

330

460

19,5

RFA
DXF