Šis produktas yra nutrauktas
Šis produktas buvo pakeistas  AES3.2-0,9KW, SS, control unit

AES-0,9KW, SS Valdymo blokas

Prekės Numeris: 35551

• Oro ir dūmų ištraukimo skirstomasis įrenginys su perjungimu atskiroms apvijoms.

• Visos funkcijos atitinka VDMA 24177 / DIN / VDE 0660 standartus

• Plastikinis korpusas

• Variklio apsaugos srovės diapazonas (standartiškai): 0,6 iki 1,0A / 1,6 iki 2,4A (kitoks srovės diapazonas turi būti tiksliai nurodytas prieš pateikiant užsakymą).

Oro ir dūmų ištraukimo skirstomasis įrenginys su perjungimu atskiroms apvijoms, skirtas vienam ventiliatoriui su trifaziu, iki 0,9 kW galingumo varikliu; plastikinis korpusas a/b/g 400/320/190mm.

Pasirinkus įmanoma įjungti du ventiliatorius. Žr. šio valdymo bloko aprašą 35593.

Techniniai parametrai

Išmatavimai ir svoriai
Svoris 0 kg

Exhaust air and smoke extraction switchgear for one "three-phase motor" up to 0,9 KW with switching for separate windings. In plastic housing H/W/D 400/320/190 mm.

For operational air exhaust and emergency smoke extraction circumventing the motor protection.

All functions in accordance with VDMA 24177 (Fans for keeping buildings free of smoke and heat in case of fire).

Complete switchgear implemented in accordance with DIN/VDE 0660.

Functions:

• With integrated emergency-stop/main switch sealable in the on position and lockable in the Off position

• With load contactor and motor protection relay for fan motor

• Start-up and coasting circuit for two-stage fan from 7.5 KW

• With safety low voltage power supply for 15 external sensors/alarms

• With control current fuses for internal and external consumers

• With standard assembly with quiescent current logic for linking all switching and function requests for operating mode and switching position priority plus compulsory activation of max. fan power in smoke extraction mode

• With self-latching trip for automatic smoke alarms

• With operating mode switch and displays on the front panel for ready / running / smoke extraction / unlock and overload

• Inputs for external control points and sensors such as fire brigade switch / ventilation switch / pushbutton alarm / automatic smoke alarm / fire alarm

• Outputs for fan motor / ventilation flap selectively with open/return signal for fan activation / floating and non-floating operating mode signals / low voltage output

Completely pre-wired and tested ready for connection!

All power and control voltage connections fed to connecting terminals installed in a plastic housing.

Protection rating 2, protection class IP 54 indoor, industrial manufacturing quality, color 7035 grey.

With cable gland in adapted size for each cable.

With CE marking.

Including impact-proof transport packaging.

Dokumento failo pav Dokumento failo tipas
Vadovas
Elektros jungimai
Elektros jungimai
Deklaracija
Deklaracija
Kita