Sistema di regolazione semplificata motori EC (CO2 e T)
Numero articolo: 24808
• Simple to install, connect and set up
• 50/60HZ mains option
• Can be used with all 220V single phase and 380V three phase EC fans
• Built in sensors
• Conforms to CE standards EN 60730-1, EN 61000-6-3, EN 61000-6-1
• Demand control made simple
The controller compares room temperature with an adjustable set point (knob) and regulates a 0..10 V proportional integral INTERNAL 1 SIGNAL in direct or reverse action based on jumper JP1 setting:
JP1 closed 1-2 = heating (reverse action)
JP1 closed 2-3 = cooling (direct action)
The controller compares also CO2 with an adjustable set point (SW3) and regulates a 0..10 V proportional INTERNAL 2 SIGNAL in direct action.
The output signal applied to a ventilator is the maximum between INTERNAL 1 SIGNAL and INTERNAL 2 SIGNAL.
The range for temperature knob set point is from 5 to 30°C
| Dati nominali | ||
|---|---|---|
| Voltaggio nominale | 85 a 265 | V | 
| Frequenza | 50; 60 | Hz | 
| Potenza in entrata | 2 | W | 
| Temperatura | -20 a 50 | °C | 
| Temperatura stabilita | 5 a 30 | °C | 
| Protezione/Classificazione | ||
|---|---|---|
| Classe di protezione | IP30 | 
| Dimensioni e pesi | ||
|---|---|---|
| Peso | 0,147 | kg | 
| Altri | ||
|---|---|---|
| Misura del CO2 | 0 a 2.000 | ppm | 
            | Nome documento | Tipo documento | |
|---|---|---|
| IMO_EC-BASIC_EN_SV_REV3.PDF | Manuale | |
| 24808_Declaration of Conformity_EN.pdf | Dichiarazione |