RVK-EX 315D4

Item number: 237943

According to ATEX Directive 2014/34/EU

Speed controllable

Can be installed in any position

Motorprotection over cold conductor

The RVK fans are designed for installation in ducts. The fans have backward curved blades and external rotor motors.

The RVK-EX 315D4 can be controlled by reducing voltage via 5-step controller in combination with the Systemair Standard tripping unit U-EK230E EX.

The RVK-EX 315D4 fan complies with the ATEX regulation. The fans could be used for zone 1 and zone 2; Field of application for gases of groups IIA, IIB and also hydrogen, temperature class T1, T2 and T3. The casing is made from conducting plastic. The fans are certified under the no TPS 20 ATEX 085751 0009 X.

Explosion proof version comply with EN 60079-0, EN 60079-7, EN 14986, DIN EN ISO 80079-36 and DIN EN ISO 80079-37.

NB. Motor protection device U-EK230E EX must always be connected.

Tehnički parametri

Nominalni podaci
Napon (nazivni) 400 V
Frekvencija 50 Hz
Faze 3~
Ulazna snaga 84 W
Ulazna struja 0,2 A
Brzina rotora 1.385 rpm
Protok zraka maks 1.120 m³/h
Temperatura transportiranog zraka maks 40 °C
Maksimalna temperatura transportiranog zraka, kada je brzinski reguliran 40 °C
Podaci o zvuku
Razina zvučnog tlaka na 3m (20m² Sabine) 41 dB(A)
Zaštita/Klasifikacija
Klasa zaštite, motor IP44
Klasa izolacije B
Oznaka za eksplozijsku otpornost II 2G Ex h IIB+H2 T3 Gb
Potvrda TPS 20 ATEX 085751 0009 X
Temperatura okoline i kanala
Temperatura okoline i kanala -20 do 40 °C
Dimenzije i težine
Dimenzija kanala; Kružni ulaz 315 mm
Dimenzija kanala; Kružni, izlaz 315 mm
Masa 7 kg
Ostali
Vrsta priključka kanala Okruglo
Naziv boje, kućište Fekete
Vrsta motora AC
Images Dimensions - RVK-EX 315D4 - Systemair

 

 

 

 

 

 

 

 

øA

øB

C

D

E

F

G

RVK-EX 315

314

405

264

30,5

225

200

60

The box is made out of conductive plastics.

The fan has a backward- curved radial impeller made out of powder-coated steel plate.

The actuation is carried out by an explosion- proofed, speed-controllable external rotor motor with PTC.

For annealing the motor is situated inside the air flow.

Motor completely with impeller statically and dynamically weigh heavy according to DIN ISO 1940.

Tested according to ATEX- Guideline 2014/34/EU.

For the extraction of potentially explosive atmosphere of zone 1, category 2G and zone 2, category 3G.

Field of application for gases of groups IIA, IIB and hydrogen.

Clasification: II 2G Ex h IIB+H2 T3 Gb

Appurtenances for the Ex- fan is available on enquiry.

ATEX-approval number TPS 20 ATEX 085751 0009 X.

R-DK4 KT 5-STOP. REGULATOR - Systemair
Item number: 6051
R-DK4 KT 5-STOP. REGULATOR .
RTRD 2 5-BRZINSKI REGULATOR - Systemair
Item number: 5941
RTRD 2 5-BRZINSKI REGULATOR .
RTRDU 2 5-BRZINSKI REGULATOR - Systemair
Item number: 5945
RTRDU 2 5-BRZINSKI REGULATOR .
SG 315 ZAćTITNA MREžA - Systemair
Item number: 5611
SG 315 ZAćTITNA MREžA .
U-EK 230E TERMOKONT.RELEJ ZA E - Systemair
Item number: 30199
U-EK 230E TERMOKONT.RELEJ ZA E .
REV-3POL ATEX 11kW-25A ON/OFF - Systemair
Item number: 36414
REV-3POL ATEX 11kW-25A ON/OFF .
FK 315 SPONA - Systemair
Item number: 1613
FK 315 SPONA .
EX PRIKLJUčNA DOZA - Systemair
Item number: 2704
EX PRIKLJUčNA DOZA .