Kit préchauf. Topvex CB315 EL

N° article: 131010

A pre-heater is available as an accessory for Systemair Topvex units with counter flow heat exchanger. The pre-heater will compensate the lack of reheater capacity during bypass de-icing.

The pre-heater is connected to the Topvex Corrigo control and will be engaged only (default*) during bypass defrosting mode, to secure supply temperature. Depending of air flow and heating coil capacity the set point for the pre-heater can be set and optimized from the Corrigo control. (Set point is determined according to lack of reheater capacity during bypass de-icing.)

*(optional function settings can be selected from Corrigo menu. In example, conditioned outdoor air temperature)

The kit contains of 1 expansion module, 1 pre-heater, 1 outdoor air sensor and 1 instruction.

Paramètres techniques

Unité
Fréquence 50 Hz
Tension (nominale) 400 V
Phases 3~
Type de tension AC
Intensité 13 A
Puissance installée 9 000 W
Débit d'air min. 420 m³/h
Température ambiante max 30 °C
Type de produit Chauffage électrique
Connexions
Type de connexion Circulaire
Conduit Circul d'aspiration 315 mm
Conduit Circul de refoulement 315 mm
Dimensions et poids
Poids 7 kg
Images Dimensions - Kit préchauf. Topvex CB315 EL - Systemair
ø D = 315 mm
FFR 315 Cassette sans Filtre - Systemair
N° article: 1779
FFR 315 Cassette sans Filtre .