PH Topvex 12kW 500x400

Batterie de préchauffage pour Topvex SC TC 35

N° article: 235133

A pre-heater is available as an accessory for Topvex units of model SC20-70 and TC20-70 with counterflow heat exchanger. The pre-heater can be used to lift the inlet temperature into the air handling unit. The pre-heater will act with supporting capacity during conditions as by pass defrosting or during low outdoor temperatures, to secure desired supply temperature.

The pre-heater is controlled from the integrated control system in the Topvex unit, Systemair Access, with a dedicated pre-heater function offering set point to actual needs.

 

 

 

Paramètres techniques

Données nominales
Tension (nominale) 400 V
Type de tension AC
Fréquence 50 Hz
Phases 3~
Puissance installée 12 000 W
Intensité 17,3 A
Débit d'air 1 080 à 7 200 m³/h
Plage de température, ambiante et conduit
Température ambiante max 30 °C
Dimensions et poids
Dimension du conduit, entrée (hauteur x largeur) 400 x 500 mm
Dimension du conduit, sortie (hauteur x largeur) 400 x 500 mm
Poids 23,45 kg
Autres
Conduit chaud/froid Chauffage électrique
Type de connexion Rectangulaire
Images Dimensions - PH Topvex 12kW 500x400 - Systemair

B

H

D

500

400

500