Toote number: 218859
TFC is a roof fan intended for residential and commercial buildings. It has energy efficient EC-fans which enables demand control. This roof fan has a simple and user friendly swing out function that will make maintenance easier for the user. The TFC is available in the colors red and black.
There are two versions of this roof fan:
The S-version comes with potentiometer as standard which allows the fan speed to be controlled stepless from 0 – 100 %. This is a simple solution when demand control is not necessary.
Possibility to communication via Modbus from size TFC 355S to TFC 560S
The P-version has Variable Air Volume (VAV), pressure control with outdoor compensation, as standard but is prepared for and can easily be converted to Constant Air Volume (CAV).
Possibility to communication via Modbus for all P versions.
Features:
• Safety switch easily accessible on the outside of the casingNominal data | ||
---|---|---|
Voltage (nominal) | 400 | V |
Sagedus | 50 | Hz |
Faas(id) | 3~ | |
Sisendvõimsus | 1 332 | W |
Sisendvool | 2.04 | A |
Ventilaatori labade kiirus | 1 382 | rpm |
Õhuhulk | Max 2 564 | L/s |
Teisaldatava õhu temperatuur | Max 60 | °C |
Max Teisaldatava õhu temperatuur kiiruse reguleerimise korralt | 60 | °C |
Müra andmed | ||
---|---|---|
Helirõhutase 10 m kaugusel (vaba levi) | 41 | dB |
Helirõhutase 4 m kaugusel(vaba levi) | 49 | dB |
Andmed vastavalt ErP | ||
---|---|---|
ErP valmidus | ErP 2018 |
Mõõtmed ja kaal | ||
---|---|---|
Kaal | 71.1 | kg |
Muud | ||
---|---|---|
Värvi nimi, korpus | punane |
Toode | ||
---|---|---|
Ärinimi | Systemair | |
Toote nimi | TFC 500 |
Ökodisaini | ||
---|---|---|
ErP vastavus | 2018 | |
Seadme kategooria | NRVU | |
Ajam | Integreeritud VSD | |
Seadme tüüp | UVU | |
Soojustagastuse tüüp | Mitte ükski | |
Temperatuuri suhe (UVU) | Pole saadaval | |
QV nom | 1.41 | m³/s |
P nom | 1.325 | kW |
PS nom | 548 | Pa |
Ventilaatori effektiivsus | 58.3 | % |
Väline leke | 0 | % |
Helivõimsuse tase LWA | 69 | dB(A) |
1 | Safety switch | 2 | Fan control | 3 | Alarm | ||
RD |
Red |
GN |
Green |
NC/WH1 |
Alarm output |
||
YE |
Yellow |
BN |
Brown |
C/WH2 |
Normally closed |
||
BU |
Blue |
GY |
Grey |
||||
WH |
White |
BK |
Black |
||||
Switch-over contact enables: |
|||||||
Voltage off |
Setpoint 1 active |
||||||
Voltage on |
Setpoint 2 active |
. |
☐A | ☐B | C | ☐D | E | F | G | øH | I |
TFC 225 | 413 | 422 | 281 | 330 | 435 | 266 | 49 | 195 | M8 |
TFC 280 | 514 | 523 | 333 | 450 | 535 | 368 | 86 | 245 | M10 |
TFC 355 | 618 | 627 | 376 | 535 | 637 | 491 | 150 | 300 | M10 |
TFC 450 | 924 | 934 | 531 | 840 | 946 | 650 | 76 | 375 | M10 |
TFC 500 | 924 | 934 | 531 | 840 | 946 | 695 | 200 | 400 | M10 |
TFC 560 | 924 | 934 | 531 | 840 | 946 | 744 | 279 | 470 | M10 |