Item number: 24808
• Simple to install, connect and set up
• 50/60HZ mains option
• Can be used with all 220V single phase and 380V three phase EC fans
• Built in sensors
• Conforms to CE standards EN 60730-1, EN 61000-6-3, EN 61000-6-1
• Demand control made simple
The controller compares room temperature with an adjustable set point (knob) and regulates a 0..10 V proportional integral INTERNAL 1 SIGNAL in direct or reverse action based on jumper JP1 setting:
JP1 closed 1-2 = heating (reverse action)
JP1 closed 2-3 = cooling (direct action)
The controller compares also CO2 with an adjustable set point (SW3) and regulates a 0..10 V proportional INTERNAL 2 SIGNAL in direct action.
The output signal applied to a ventilator is the maximum between INTERNAL 1 SIGNAL and INTERNAL 2 SIGNAL.
The range for temperature knob set point is from 5 to 30°C
Datos nominales | ||
---|---|---|
Tension nominal | 85 Para 265 | V |
Frecuencia | 50; 60 | Hz |
Potencia de entrada | 2 | W |
Temperatura | -20 Para 50 | °C |
Punto de ajuste de temperatura | 5 Para 30 | °C |
Proteccion/Clasificacion | ||
---|---|---|
Grado de proteccion | IP30 |
Dimensiones y pesos | ||
---|---|---|
Peso | 0,147 | kg |
Otros | ||
---|---|---|
Medida de CO2 | 0 Para 2.000 | ppm |