VBC 160-2 Water heating batt

Art. no.: 5458

• Removable cover for cleaning the unit.
• 2-rows battery
• Max operating temperature 150 °C
• Max operating pressure 1,0 MPa (10Bar. Tested at 16Bar.)
• The water-heating battery can be installed in a horizontal or a vertical duct with optional direction of airflow.
• Casing made of magnesium/zinc-treated steel sheet, heat transmission element with copper tubes and aluminium fins.
• Water-heating battery for heating air in ventilation systems with circular ducts.

Technical parameters

Dimensions and weights
Duct dimension; Circular, inlet 160 mm
Duct dimension; Circular, outlet 160 mm
Weight 5.4 kg
Others
Duct cooler/heater Heater coil, water
Duct connection type Circular
Images Performance - VBC 160-2 Water heating batt - Systemair

 

Air flow (m3/s)

Pressure drop (Pa)

ΔT air at T water 60/40, ˚C

Water flow rate (l/s)

Water speed (m/s)

Pressure drop (kPa)

Power (kW)

ΔT air at T water 90/70, ˚C

Water flow rate (l/s)

Water speed (m/s)

Pressure drop (kPa)

Power (kW)

VBC 100-2 VBC 125-2 VBC 160-2 VBC 200-2 VBC 250-2 VBC 315-2 VBC 400-2 VBC 500-2

0.04

0.06

0.1

0.15

0.25

0.39

0.63

0,9

35

72

40

73

68

69

77

45

16.0

13.0

19.9

17.3

17.5

18.1

17.7

19,4

0.01

0.01

0.03

0.04

0.07

0.11

0.18

0,28

0.15

0.2

0.4

0.6

0.5

0.5

0.6

0.7

0.1

0.1

3

5

3

3

4

6,6

0.85

1.0

2.6

3.5

5.7

9.2

14.6

22,7

32.5

28.3

35.8

30.4

31.7

32

31

31

0.02

0.03

0.06

0.07

0.13

0.20

0.31

0.31

0.3

0.4

0.8

1.1

0.9

1.0

1.1

1.1

1

1

8

13

7

8

10

10

1.7

2.2

4.6

6.1

10.3

16.3

25.5

25.5

Images Dimensions - VBC 160-2 Water heating batt - Systemair
ØD B H Ødy F G K L

160

313

255

10

212

40

276

356

AQUA 24TF Heat Regulator - Systemair
Art. no.: 5136
AQUA 24TF Heat Regulator .
Optigo OP 10 - Systemair
Art. no.: 7282
Optigo OP 10 .
TG-A1/PT1000 Surface sensor - Systemair
Art. no.: 7284
TG-A1/PT1000 Surface sensor

.

.
TG-A130 Surface sensor 0-30°C - Systemair
Art. no.: 5159
TG-A130 Surface sensor 0-30°C .
TG-K330 Duct Sensor 0-30°C - Systemair
Art. no.: 5160
TG-K330 Duct Sensor 0-30°C .
TG-K360 Duct sensor 0-60°C - Systemair
Art. no.: 4846
TG-K360 Duct sensor 0-60°C

for heating regulator HRG

.
Argus-RC-DO Room Controller - Systemair
Art. no.: 2916
Argus-RC-DO Room Controller

Stand alone room controllers 24/ 0-10V

.
Optigo OP 10-230 - Systemair
Art. no.: 7283
Optigo OP 10-230 .
Optigo OP 5 - Systemair
Art. no.: 13891
Optigo OP 5 .
RVAZ4 24A Actuator 0-10V - Systemair
Art. no.: 9862
RVAZ4 24A Actuator 0-10V .
RVAZ4-24 Actuator 3points - Systemair
Art. no.: 9798
RVAZ4-24 Actuator 3points

24 V AC

.
ZTR 15-0,6 valve 3-way - Systemair
Art. no.: 6573
ZTR 15-0,6 valve 3-way

DN 15 Kvs 0,6

.
ZTV 15-0,6 2-way valve - Systemair
Art. no.: 6571
ZTV 15-0,6 2-way valve

DN 15 Kvs 0,6

.