silencer, for air handling units
Art. no.: 311356
Silencer
silencer RSA(F) for use together with axial fans of AXC-Range. For effective noise suppress the silencer should be mounted directly before or after the fan. The silencers is supplied with a flange according Eurovent 1/2.
Temperature resistance: 400°C/2h
Dimensions and weights | ||
---|---|---|
Weight | 19.2 | kg |
Noise suppression dB (mid-frequency Hz) |
|
125 | 250 | 500 | 1k | 2k | 4k | 8k |
RSA(F) 450/450 |
1 |
4 |
12 |
12 |
9 |
6 |
6 |
RSA(F) 450/675 |
1 |
6 |
17 |
17 |
13 |
9 |
8 |
RSA(F) 450/900 |
1 |
7 |
21 |
21 |
15 |
10 |
8 |
Acoustic data tested in accordance to ISO 7235
(test report number 9580180)
|
Ø I | Ø E | Ø F | A x B | L |
RSA(F) 450/675 |
450 |
610 |
500 |
8 x M10 |
675 |