Smoke Control Damper AAmulti
Art. no.: A-S-BA2
S-BA2 smoke control dampers operate with mechanical or natural smoke and heat extraction systems. They remove poisonous gases, smoke and fire and can also supply clean air to fire compartments.
S-BA2 dampers have an actuator without a spring. Thus, they have two safety positions: an “open” position and a “closed” one. Power is necessary for the smoke control dampers.
The “Installation Methods” section shows the types of installations that are permitted.
Special Properties• Body length only 145 mm and no blade overhangs.
• You can install the smoke control damper into walls or on ducts.
• The S-BA2 dampers classified “multi” can also operate in compartments that are identified as "single”.
• The pressure level is 2 (-1000 Pa ... 300 Pa).
• The casing leakage class C (complient with EN 1751).
Fire ResistivityS-BA2 smoke control dampers have a CE certification that meets the EU’s Construction Products Regulation and complies with Standard EN 12101-8:2011. EN 1366-10:2011, A1:2017, and EN 1366-2:2015 are the reference Standards for the tests. EN 13501-4:2016 is the reference Standard for the Classification. The smoke control damper and its installation counts as one unit for fire resistivity rating:
• Damper installed within a wall: EI 90 (vew - i↔o) S1000Cmod AAmulti
• Damper installed on the duct: EI 120 (ved - hod - i↔o) S1000Cmod AAmulti
Types of ProductThere are different types of S-BA2 connection. Thus, there are several types of grilles:
• 00 – without grille.
• 01, 02 – with grille on one side only.
• 11, 22 – with grille on both sides.
Types of Activation• B230 - Smoke control damper with an activation mechanism with a Belimo actuator (230V AC) and auxiliary switches.
• B24 - Smoke control damper with an activation mechanism with a Belimo actuator (24V AC/DC) and auxiliary switches.
• B24-W - Smoke control damper with an activation mechanism with a Belimo actuator (24V AC/DC) and auxiliary switches, with provided cable connectors for the supply and communication unit (communication unit not part of the mechanism).
• B24-SR - Smoke control damper with an activation mechanism with a modulating Belimo actuator (24V AC/DC; 0(2) V...10 V DC) and auxiliary switches. Modulating actuators have the possibility to open the blade at a desired angle.
• BST0 - Smoke control damper with an activation mechanism with a Belimo actuator (AC/DC 24 V, supply through communication unit: AC 230 V) and with a Belimo supply and communication unit BKNE230-24 (other communication units on demand).
• BST1 - Smoke control damper with an activation mechanism with a Belimo actuator (AC/DC 24 V), with supply and communication unit (SLC powered) BC24-G2 (THC).
• BST10 - Smoke control damper with an activation mechanism with a Belimo actuator (AC/DC 24 V), with supply and communication unit (AC 230 V) BKNE230-24-PL (Powerline).
Other communication units are possible on demand.
DesignThe casing of the S-BA2 is made of a galvanized sheet metal. Blades and mechanism access doors are made from calcium silicate boards. A foam seal with an intumescent seal that prevents leaks of heat or smoke. The casing has flanges on two sides with a thread to attach to sheet-metal duct flanges. Two sides of the damper have inserts with a thread to attach the grille. The damper casing and two covers on two sides give protection to the mechanism and the actuator of the S-BA2. They also give access for easy connection.
Composition of materialsThe product contains these materials:
• Galvanized sheet metal
• Calcium silicate board
• Polyurethane foam
• Intumescent strips,
• PE tapes and foil,
• Galvanized steel fasteners,
• Acrylic sealant
The manufacturing processes of these materials agree with local regulations. The product does not contain dangerous materials.
Dimensions and weights | ||
---|---|---|
Weight | 1 | kg |
Document filename | Document filetype | |
---|---|---|
1396-CPR-0202_E | deGanymed_mediaType_Image | |
DeclarationOfPerformance_S-BA2_A_EN__signed_ | deGanymed_mediaType_Image | |
HandBook_S-BA2_EN_2022-07-11 | deGanymed_mediaType_Image | |
OperatingJournal_SmokeDampers_EN_202204 | deGanymed_mediaType_Image |