Preheat.kit Topvex CB315 EL

Art. no.: 131010

A pre-heater is available as an accessory for Systemair Topvex units with counter flow heat exchanger. The pre-heater will compensate the lack of reheater capacity during bypass de-icing.

The pre-heater is connected to the Topvex Corrigo control and will be engaged only (default*) during bypass defrosting mode, to secure supply temperature. Depending of air flow and heating coil capacity the set point for the pre-heater can be set and optimized from the Corrigo control. (Set point is determined according to lack of reheater capacity during bypass de-icing.)

*(optional function settings can be selected from Corrigo menu. In example, conditioned outdoor air temperature)

The kit contains of 1 expansion module, 1 pre-heater, 1 outdoor air sensor and 1 instruction.

Technical parameters

Unit
Frequency 50 Hz
Voltage (nominal) 400 V
Phases 3~
Voltage type AC
Input current 13 A
Input power 9,000 W
Air flow min. 420 m³/h
Permitted ambient temperature max 30 °C
Product type Electric heater
Connections
Duct connection type Circular
Duct dimension; Circular, inlet 315 mm
Duct dimension; Circular, outlet 315 mm
Dimensions and weights
Weight 7 kg
Images Dimensions - Preheat.kit Topvex CB315 EL - Systemair
ø D = 315 mm
FFR 315 Filter cassette - Systemair
Art. no.: 1779
FFR 315 Filter cassette .