Rectangular, for air handling units
Art. no.: 9241
Description
LDR-B is fitted with built-in baffles and side baffles located outside the fitting dimensions.
Design
LDR-B has an external shell of trapezoidal corrugated sheet for stability and reduced risk of natural oscillation. LDR-B is designed for low air resistance with baffle combinations that dampen particularly low-frequency noise well. The type of insulation material is Lindtec which has been developed to provide good noise properties, low weight and to be cleanable. LDR-B meets the requirements of air tightness class C and pressure class 2 according to EN 1507:2006.
Dimensions and weights | ||
---|---|---|
Duct dimension, inlet (height x width) | 400 x 600 | mm |
Duct dimension, outlet (height x width) | 400 x 600 | mm |
Weight | 34.7 | kg |
Others | ||
---|---|---|
Duct connection type | Rectangular |
Noise suppression dB (mid-frequency Hz) |
|
63 |
125 |
250 |
500 |
1k |
2k |
4k |
8k |
LDR-B 40-20 |
4 |
12 |
21 |
38 |
46 |
34 |
25 |
19 |
LDR-B 50-25 |
4 |
12 |
20 |
34 |
36 |
27 |
19 |
14 |
LDR-B 50-30 |
4 |
12 |
20 |
34 |
36 |
27 |
19 |
14 |
LDR-B 50-40 |
4 |
12 |
20 |
34 |
36 |
27 |
19 |
14 |
LDR-B 60-30 |
4 |
12 |
20 |
30 |
29 |
22 |
16 |
12 |
LDR-B 60-40 |
4 |
12 |
20 |
30 |
29 |
22 |
16 |
12 |
LDR-B 70-30 |
5 |
12 |
19 |
27 |
25 |
18 |
13 |
10 |
LDR-B 70-40 |
5 |
12 |
19 |
27 |
25 |
18 |
13 |
10 |
LDR-B 80-35 |
4 |
11 |
16 |
22 |
19 |
14 |
10 |
8 |
LDR-B 80-40 |
4 |
11 |
16 |
22 |
19 |
14 |
10 |
8 |
LDR-B 90-50 |
3 |
9 |
16 |
26 |
27 |
20 |
14 |
11 |
LDR-B 100-35 |
4 |
11 |
18 |
27 |
27 |
20 |
14 |
11 |
LDR-B 110-60 |
5 |
12 |
19 |
28 |
27 |
20 |
14 |
11 |
LDR-B 120-60 |
4 |
11 |
17 |
24 |
22 |
16 |
12 |
9 |
a | b | l |
600 |
400 |
1260 |