LDC 200-900 Silencer

Round, for air handling units

Art. no.: 5195

Silencer

Easily-fitted silencer for circular ducts, fitted with a connection that complies with the spiral duct standard. The LD effectively reduces noise in the duct. Two silencers can be used together in installations where noise reduction is a particularly strong requirement. This is very effective. For the most effective noise reduction, the silencer should be fitted immediately behind a fan or bend. The silencer should be used together with an insulated fan where there is a requirement for noise reduction both in the duct and in the surroundings as a whole. Insulation thickness 50 mm.

Energy class label

Energy class, Local demand
Material Declaration, BVB, Acceptable 0
Material Declaration, Sunda Hus, Level A or B 0
EPD 0

Technical parameters

Dimensions and weights
Length 900 mm
Weight 8.9 kg

Pressure drop

Images Performance - LDC 200-900 Silencer - Systemair
Noise suppression dB (mid-frequency Hz)

 

63 125 250 500 1k 2k 4k 8k

LDC 100-300

2

2

6

14

21

25

20

11

LDC 100-600

4

3

11

24

36

49

34

17

LDC 100-900

5

4

15

34

50

50

48

23

LDC 100-1200

6

5

19

45

50

50

50

29

LDC 125-300

2

2

6

13

16

20

15

10

LDC 125-600

3

3

9

23

30

40

22

14

LDC 125-900

4

4

12

33

45

50

30

17

LDC 125-1200

5

5

15

43

50

50

38

21

LDC 150-300

1

2

4

10

12

15

8

8

LDC 150-600

-

3

7

20

27

31

16

11

LDC 160-300

1

2

4

10

12

15

8

8

LDC 160-600

2

3

7

19

27

29

14

11

LDC 160-900

2

4

10

28

42

43

20

15

LDC 200-300

1

2

5

8

10

11

5

5

LDC 200-600

2

3

7

16

21

23

9

8

LDC 200-900

2

4

8

24

32

34

13

10

LDC 250-600

3

2

7

13

17

16

8

6

LDC 250-900

3

4

8

20

26

23

10

8

LDC 315-600

0

2

6

11

14

9

4

5

LDC 315-900

1

3

7

16

22

12

6

7

LDC 355-900

-

3

6

13

18

10

6

7

LDC 400-900

1

3

5

10

13

7

5

6

Images Dimensions - LDC 200-900 Silencer - Systemair

L nom

ø di

ø d0

l

900

 

200

 

300

 

985