Centrifugal roof fan, vertical discharge
Art. no.: 36202
Speed-controllable
Integral thermal contacts
Low sound level
Maintenance-free and reliable
The DVS/DHS/DVSI models have impellers with backward curved blades and external rotor motors. All motors are speed controllable over the voltage. For speed controlling of the DVS/DHS/DVSI roof fans with a frequency converter a type with all pole sine filter is needed! The motors are suspended on effective vibration dampers.
DVS/DHS/DVSI …EZ / EV / ES: 1~ motor with connection for 2-speeds
DVS/DHS/DVSI …E4: 1-speed motor
DVS/DHS/DVSI …DV / DS: 3~ with Y/D-connection for 2-speeds
To protect the motors from overheating the DVS/DHS/DVSI up to size 311 have integral thermal contacts, from size 355 with external leads for connection to a motor protection device.
The casing is made from aluminum and the base frame from galvanised steel. Suitable for coastal applications. The impellers up to size 355 are manufactured from polyamide PA6 25GV, from size 400 in aluminum.
DVS with outlet vertical
DHS with outlet horizontal
DVSI has a 50 mm mineral wool insulation for low noise level.
Product | ||
---|---|---|
Trade name | Systemair | |
Product name | DVS 710DS Roof fan |
Ecodesign | ||
---|---|---|
ErP compliance | 2018 | |
Unit category | NRVU | |
Drive | External MSD or VSD | |
Unit type | UVU | |
Heat recovery type | None | |
Temperature ratio (UVU) | Not applicable | |
qv nom | 2.421 | m³/s |
P nom | 2.04 | kW |
Ps nom | 437 | Pa |
Fan efficiency | 51 | % |
External Leakage | 0 | % |
Sound power level LWA | 81 | dB(A) |
Nominal data | ||
---|---|---|
Voltage (nominal) | 400 | V |
Frequency | 50 | Hz |
Phase(s) | 3~ | |
Input power | 2,040 | W |
Input current | 4.04 | A |
Impeller speed | 909 | rpm |
Air flow | max ; 4,035; | L/s |
Temperature of transported air | max 40 | °C |
Max temperature of transported air, when speed controlled | 40 | °C |
Sound data | ||
---|---|---|
Sound pressure level at 10m (free field) | 50 | dB(A) |
Sound pressure level at 4m (free field) | 58 | dB(A) |
Protection/Classification | ||
---|---|---|
Enclosure class, motor | IP54 | |
Insulation class | F |
Data according to ErP | ||
---|---|---|
ErP ready | ErP 2016; ErP 2018 |
Dimensions and weights | ||
---|---|---|
Weight | 112 | kg |
Others | ||
---|---|---|
Motor type | AC |
Hz | Tot | 63 | 125 | 250 | 500 | 1k | 2k | 4k | 8k | |
LwA Inlet |
dB(A) |
79 |
66 |
68 |
73 |
74 |
74 |
70 |
65 |
57 |
LwA Surrounding |
dB(A) |
81 |
68 |
70 |
75 |
76 |
76 |
72 |
67 |
59 |
with SSD 710 |
||||||||||
LwA Inlet |
dB(A) |
69 |
63 |
62 |
65 |
60 |
54 |
45 |
42 |
46 |
Measuring point: qv = 2,42 m³/s, Ps = 437 Pa |
Mid-frequency band, Hz |
* diameter D refers to scew-hole-circuit H |
DVS |
□A |
□B |
C |
øD |
□E |
□F |
G |
H |
øI |
710 |
1350 |
1185 |
660 |
674 |
1035 |
840 |
320 |
8xM8 |
14(4x) |
.
16A, 400V, IP20, switch cabinet instalation, TK, 54x80x83mm
indication of angle with order ... °, for air handling units
indication of angle with order ... °, for air handling units
985x985x800mm, alu, sea water resis., for air handling units