Fire dampers represent passive fire protection and are designed to utilize compartmentalization to prevent the spread of toxic gases, smoke and fire. The opening and closure of the damper blade can be activated remotely for actuator versions. In case of fire when the air in the duct exceeds 72 °C or 74 °C, the thermal fuse melts in both actuator and manual versions. The melting of the thermal fuse activates the closure of the damper blade automatically. The damper blade is then mechanically locked in the closed position.

Highlights

• Short body without blade overhangs

• Can be used as Air-transfer grille with cold smoke tightness

• Duct connection from both sides always available

• Symmetric structure and mechanism accessible from both sides

• Fit installation, filling not visible

• Available with smoke detection

• One sided duct connection ended with Grille

Fire Resistivity

F-B90 fire dampers are CE certified following the Construction Products Regulation according to EN 15650:2010. Dampers are tested according to EN 1366-2:2015 and classified according to EN 13501-3 + A1:2009. The fire damper together with its installation form an inseparable part of the fire resistivity rating. F-B90 fire dampers are designed for the installations listed and described in their Handbook.

• Damper connected to duct on both sides or on one side only, installed within standard supporting construction in accordance with EN 1366-2:2015: EI90 (ve - ho i↔o)S

• Damper with grille on both sides and no duct connection (air transfer damper), installed within standard supporting construction in accordance with EN 1366-2:2015: EI90 (ve - i↔o)S & EI120 (ve - i↔o)

Types of Product

There are different types of F-B90 connection. Thus, there are several types of grilles:

• 00 – without grille.

• 01, 02 – with grille on one side only.

• 11, 22 – with grille on both sides.

Types of Activation

• H0

Fire damper with a manual crank activation mechanism and with a spring return release mechanism activated by a fusible thermal link set to 74°C.

• H2

Fire damper with an activation mechanism H0 + open and closed indication with AC 230 V or AC/DC 24 V contact switches.

• B230T or G230T (G230T not available for sizes H=250)

Fire damper with an activation mechanism with a Belimo (B230T) or Gruner (G230T) spring return actuator (230V AC) with an electro-thermal fuse 72°C and auxiliary switches.

• B24T or G24T (G24T not available for sizes H=250)

Fire damper with an activation mechanism with a Belimo (B24T) or Gruner (G24T) spring return actuator (24V AC/DC) with electro-thermal fuse 72°C and auxiliary switches.

• BST0 or GST0 (GST0 not available for sizes H=250)

Fire damper with an activation mechanism with spring return actuator Belimo (BST0, AC/DC 24 V, supply through com. unit: AC 230 V) or Gruner (GST0, AC/DC 24 V, supply through com. unit: AC 24 V) with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication unit BKN230-24 or Gruner supply and communication unit fs-UFC24-2 (other communication units on demand).

• B24T-SR or G24T-SR (G24T-SR not available for sizes H=250)

Fire damper with an activation mechanism with a Belimo (B24T-SR) or Gruner (G24T-SR) spring return actuator (24V AC/DC) with electro-thermal fuse 72°C and auxiliary switches for Modulated dampers (possibility to open the blade at the desired angle).

• BSD230T or GSD230T (Only for Grille types 11 and 22 & GSD230T not available for sizes H=250)

Overflow fire damper with Smoke Detector fitted activation mechanism (230V AC) with a Belimo or Gruner spring return actuator with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication unit or Gruner power supply unit (Actuator powered through transformer and than 24V AC/DC Smoke detector).

• BSD24T or GSD24T (Only for Grille types 11 and 22 & GSD24T not available for sizes H=250)

Overflow fire damper with Smoke Detector fitted activation mechanism (24V AC/DC) with a Belimo or Gruner spring return actuator with an electro-thermal fuse 72°C and auxiliary switches, with a Belimo supply and communication unit or Gruner power supply unit (Actuator powered through 24V AC/DC Smoke detector).

Design

The casing of the F-B90 is made of a galvanized sheet metal. Blades and mechanism access doors are made from calcium silicate boards. A foam seal with an intumescent seal that prevents leaks of heat or smoke. The casing has flanges on two sides with a thread to attach to sheet-metal duct flanges. Two sides of the damper have inserts with a thread to attach the grille. The damper casing and two covers on two sides give protection to the mechanism and the actuator of the F-B90. They also give access for easy connection.

Composition of materials

Body of the product contains these materials: Galvanized sheet metal; Galvanized steel fasteners; PE tapes and foil

Blades and mechanism access doors of the product contain these materials: Calcium silicate board; Polyurethane foam; Intumescent strips; Acrylic sealant

The manufacturing processes of these materials agree with local regulations. The product does not contain dangerous materials.