AES3.2-0,55KW,D, control unit

Art. no.: 77039

Application

The exhaust air and gas extraction control system AES-D is designed in connection with the control unit AES-ST3.2 for the operation of one stage fans in DIRECT SWITCHING (D) for the ventilation in normal operation and for emergency smoke extraction.

Function

The functionality of the control system corresponds to VDMA 24177. The main switch, which can be shut off, is horizontally placed on the outside of the control unit. It can be used as an emergency-off switch if the control unit is attached in visual proximity to the fan motor. The main switch can also be locked in the On position or sealed to prevent unintentional shut-down of the system. On the front of the operating and display module, the ventilation system can only be switched to SMOKE EXTRACTION or READY mode or to ON. OFF switching is not possible. The operating conditions are displayed optically. The overcurrent triggering must be unlocked on the motor protection device after the disturbance is eliminated. When air is being exhausted, all motor protection devices are functioning to prevent motor damage. During smoke extraction, all motor protection devices are bypassed so that the longest possible function duration can be achieved before the fan motor is destroyed.

Notes

The AES switching

device should be installed as closely as possible to the associated fan outside of the area from which smoke is to be extracted and be accessible via escape and rescue routes.

The power supply

for smoke extraction fans must be connected directly on the NSHV and designed to maintain function.

In the case of smoke extraction

, fan motors may not be operated by frequency converters or similar control devices.

Observe the permissible

motor switch-on speed / h when starting up in smoke extraction mode. Otherwise the fan motor can be destroyed due to the bypassed motor protection devices!

Smoke extraction systems

must undergo a complete function check every 3 months and be serviced once a year.

Project-related

smoke extraction switching systems, special switches, emergency power supply on request.

D2M = for 2 Motors

D3M = for 3 Motors

D4M = for 4 Motors

Technical Data

Back-up fuse installed at the site: 20A

On-site cable cross-sections: 5x2,5mm²

Control fuse: 6A

Cable entries:  8n

Label: CE

Motor protection current-range (Standard)

Power                    Current-range

0,25 - 0,37 kW         0,6A - 1,0A

0,55 kW                  1,0A - 1,6A

0,75 kW                  1,6A - 2,4A

1,1 - 1,5 kW            2,4A - 4,0A

2,2 - 3,0 kW            4,0A - 6,0A

4,0 kW                    6,0A - 9,0A

(When it is an other current-range needed, it has to be noted explicitly) 

Technical parameters

Nominal data
Voltage (nominal) 400 V
Protection/Classification
Enclosure class IP54
Controller and Sensors
Permitted ambient temperature 0 to 40 °C
Dimensions and weights
Depth 130 mm
Height 320 mm
Width 240 mm
Weight 2.2 kg
Others
Product category Other ventilation accessories
A B C

AES-D 0,25kW up to 7,5 kW

240

320

130

DVG-V 400D4-XL/F400 IE2 - Systemair
Art. no.: 9995221
DVG-V 400D4-XL/F400 IE2 .
FWS-P4 fire brigade switch - Systemair
Art. no.: 77153
FWS-P4 fire brigade switch .
FWS-P4 fire brigade switch+key - Systemair
Art. no.: 77158
FWS-P4 fire brigade switch+key .
FWS-S4 fire brigade switch - Systemair
Art. no.: 77152
FWS-S4 fire brigade switch .
FWS-ZY profile cylinder - Systemair
Art. no.: 77157
FWS-ZY profile cylinder .
HRM-3K-GE pushbutton switch - Systemair
Art. no.: 77155
HRM-3K-GE pushbutton switch .
HRM-3K-GR pushbutton switch - Systemair
Art. no.: 77154
HRM-3K-GR pushbutton switch .
HRM-3K-OR pushbutton switch - Systemair
Art. no.: 77156
HRM-3K-OR pushbutton switch .