VBR 60-35-2 Water heating batt

Art. no.: 5467

Water-heating battery

Water-heating battery for heating air in ventilation systems with rectangular ducts. Hot-zinc-coated casing, heat transmission element with copper tubes and aluminium fins. In cold conditions, a frost protection device with sensor should be fitted to reduce the risk of damage from freezing. The water-heating battery can be installed in a horizontal or vertical duct with an optional direction.

Technical parameters

Nominal data
Maximum operating temperature 150 °C
Dimensions and weights
Duct dimension, inlet (height x width) 350 x 600 mm
Duct dimension, outlet (height x width) 350 x 600 mm
Weight 8.6 kg
Others
Duct cooler/heater Heater coil, water
Maximum operating pressure at water temperature 100°C 1,600,000 Pa
Maximum operating pressure at water temperature 150°C 1,000,000 Pa
Duct connection type Rectangular

 

 

Air

 

 

 

Water

 

VBR

Water temp. (in/out)

Flow (m3/h)

Pressure drop (Pa)

ΔT

Capacity (kW)

Flow (l/s)

Pressure drop (kPa)

40-20-2 60/40ºC 400 9 18.5 2.7 0.03 0.5

 

 

1000

48

12.7

4.6

0.06

1

40-20-4

 

400

18

29.5

4.3

0.05

0.5

 

 

1000

96

19.5

7.1

0.09

0.5

40-20-2

80/60ºC

400

9

32.8

4.7

0.06

1

 

 

1000

48

24.5

8.9

0.11

2

40-20-4

 

400

18

46.3

6.7

0.08

0.5

 

 

1000

96

38.9

14.0

0.17

1

50-25-2

60/40ºC

600

8

21.7

4.7

0.06

1

 

 

1200

29

18.2

7.9

0.10

2

50-25-4

 

600

16

33.1

7.2

0.09

0.5

 

 

1200

59

28.4

12.3

0.15

1

50-25-2

80/60ºC

600

8

36.5

7.9

0.10

2

 

 

1200

29

28.6

12.4

0.15

4

50-25-4

 

600

16

54.5

11.8

0.14

1

 

 

1200

59

45.9

19.9

0.24

3

50-30-2

60/40ºC

800

10

18.2

5.3

0.06

0.5

 

 

2000

54

13.5

9.8

0.12

1

50-30-4

 

800

20

32.5

9.4

0.11

1

 

 

2000

109

27.2

19.7

0.24

2

50-30-2

80/60ºC

800

10

33.6

9.7

0.12

1

 

 

2000

54

24.3

17.5

0.21

2

50-30-4

 

800

20

53.8

15.5

0.19

1

 

 

2000

109

41.7

30.1

0.37

4

60-30-2

60/40ºC

1000

11

19.2

6.9

0.08

1

 

 

2500

58

15.4

13.9

0.17

2

60-30-4

 

1000

22

34.1

12.3

0.15

1

 

 

2500

117

28.2

25.5

0.31

4

60-30-2

80/60ºC

1000

11

34.3

12.4

0.15

1

 

 

2500

58

24.4

22.1

0.27

4

60-30-4

 

1000

22

53.9

19.5

0.24

2

 

 

2500

117

41.8

37.8

0.46

7

60-35-2

60/40ºC

1200

11

18.7

8.1

0.10

0.5

 

 

3000

61

15.0

16.3

0.20

2

60-35-4

 

1200

23

34.2

14.8

0.18

1

 

 

3000

123

28.1

30.4

0.37

4

60-35-2

80/60ºC

1200

11

33.9

14.7

0.18

1

 

 

3000

61

24.1

26.1

0.32

3

60-35-4

 

1200

23

53.6

23.2

0.28

3

 

 

3000

123

41.5

45.0

0.55

8

70-40-2

60/40ºC

2000

31

20.1

14.5

0.18

1

 

 

4000

94

16.0

23.2

0.28

1

70-40-3

 

2000

46

24.7

17.8

0.22

0.5

 

 

4000

139

21.1

30.5

0.37

1

70-40-2

80/60ºC

2000

31

34.7

25.1

0.31

1

 

 

4000

94

25.1

36.3

0.44

3

70-40-3

 

2000

46

45.4

32.8

0.40

1

 

 

4000

139

34.4

49.7

0.61

2

80-50-2

60/40ºC

2500

25

21.1

19.0

0.23

0.5

 

 

5000

77

17.2

31.1

0.38

1

80-50-3

 

2500

37

28.0

25.3

0.31

0.5

 

 

5000

113

24.0

43.4

0.52

1

80-50-2

80/60ºC

2500

25

36.8

33.3

0.41

1

 

 

5000

77

26.9

48.6

0.59

2

80-50-3

 

2500

37

48.4

43.7

0.53

1

 

 

5000

113

37.1

67.0

0.82

2

100-50-2

60/40ºC

3000

23

24.8

26.9

0.32

1

 

 

6000

72

18.4

40.0

0.48

2

100-50-3

 

3000

35

32.3

35.0

0.42

1

 

 

6000

106

25.6

55.4

0.67

2

100-50-2

80/60ºC

3000

23

38.4

41.6

0.51

2

 

 

6000

72

28.2

61.1

0.75

4

100-50-3

 

3000

35

50.1

54.3

0.66

2

 

 

6000

106

38.7

83.8

1.02

4

Images Dimensions - VBR 60-35-2 Water heating batt - Systemair
F= Thread G 1/4

G=

Airing

H=

Water out

I=

Connection for immersion sensor

J=

Water in

K=

Draining

A c/c A B c/c B E

VBR 40-20-2

438

420

238

220

R¾''

VBR 50-25-2

538

520

288

270

R¾''

VBR 50-30-2

538

520

338

320

R¾''

VBR 50-40-2

538

520

438

420

R¾''

VBR 60-30-2

638

620

338

320

R¾''

VBR 60-35-2

638

620

388

370

R¾''

VBR 70-40-2

738

720

438

420

R 1''

VBR 80-40-2

838

820

438

420

R 1''

VBR 80-50-2

838

820

538

520

R 1''

VBR 100-50-2

1038

1020

538

520

R 1''

 

 

 

 

 

 

 

A

c/c A

B

c/c B

E

VBR 40-20-4

438

420

238

220

R¾''

VBR 50-25-4

538

520

288

270

R¾''

VBR 50-30-4

538

520

338

320

R 1''

VBR 50-40-4

538

520

438

420

R 1''

VBR 60-30-4

638

620

338

320

R 1''

VBR 60-35-4

638

620

388

370

R 1''

 

 

 

 

 

 

 

A

c/c A

B

c/c B

E

VBR 70-40-3

738

720

438

420

R 1''

VBR 80-50-3

838

820

538

520

R 1''

VBR 100-50-3

1038

1020

538

520

R 1''

VBR 120-60-3

1238

1220

638

620

R 1¼"

AQUA 24TF Heat Regulator - Systemair
Art. no.: 5136
AQUA 24TF Heat Regulator .
Optigo OP 10 - Systemair
Art. no.: 7282
Optigo OP 10 .
TG-A1/PT1000 Surface sensor - Systemair
Art. no.: 7284
TG-A1/PT1000 Surface sensor .
TG-A130 Surface sensor 0-30°C - Systemair
Art. no.: 5159
TG-A130 Surface sensor 0-30°C .
TG-K330 Duct Sensor 0-30°C - Systemair
Art. no.: 5160
TG-K330 Duct Sensor 0-30°C .
Antifrost thermostat FT30 - Systemair
Art. no.: 332795
Antifrost thermostat FT30 .
Argus-RC-DO Room Controller - Systemair
Art. no.: 2916
Argus-RC-DO Room Controller .
Optigo OP 10-230 - Systemair
Art. no.: 7283
Optigo OP 10-230 .
Optigo OP 5 - Systemair
Art. no.: 13891
Optigo OP 5 .
RVAZ4 24A Actuator 0-10V - Systemair
Art. no.: 9862
RVAZ4 24A Actuator 0-10V .
RVAZ4-24 Actuator 3points - Systemair
Art. no.: 9798
RVAZ4-24 Actuator 3points .
TG-D1/PT1000 Immersion sensor - Systemair
Art. no.: 6773
TG-D1/PT1000 Immersion sensor .
ZTR 20-4,0 valve 3-way - Systemair
Art. no.: 9678
ZTR 20-4,0 valve 3-way .
ZTV 20-4,0 2-way valve - Systemair
Art. no.: 9826
ZTV 20-4,0 2-way valve .