RS 60-35 L3 sileo

Art. no.: 39631

Swing out function of the motor for easy maintenance

Speed-controllable

Integral thermal contacts

Can be installed in any position

Maintenance-free and reliable

The RS models have impellers with backward-curved blades and external rotor motors. The motor and impeller are mounted on the access cover to facilitate easy maintenance. To protect the motor from overheating the RS has integral thermal contacts with external leads for connection to a motor protection device. The fan can be installed in any position and is easy to connect using the DS flexible connections. The casing is manufactured from galvanised sheet steel.

Ecodesign

Product
Trade name Systemair
Product name RS 60-35 L3 V-wheel rec. fan
Ecodesign
ErP compliance 2018
Unit category NRVU
Drive External MSD or VSD
Unit type UVU
Heat recovery type None
Temperature ratio (UVU) Not applicable
qv nom 0.589 m³/s
P nom 0.464 kW
Ps nom 330 Pa
Fan efficiency 41.9 %
External Leakage 5 %
Sound power (LWA) 66 dB(A)

Technical parameters

Nominal data
Voltage (nominal) 400 V
Frequency 50 Hz
Phases 3~
Input power 537 W
Input current 1.25 A
Impeller speed 1,413 rpm
Air flow max 4,244 m³/h
Temperature of transported air max 70 °C
Max temperature of transported air, when speed controlled 70 °C
Sound data
Sound pressure level at 3m (20m² Sabin) 59 dB(A)
Protection/Classification
Enclosure class, motor IP54
Insulation class F
Data according to ErP
ErP ready ErP 2018
Dimensions and weights
Duct dimension, inlet (height x width) 350 x 600 mm
Duct dimension, outlet (height x width) 350 x 600 mm
Weight 32 kg
Others
Duct connection type Rectangular
Motor type AC
Images Dimensions - RS 60-35 L3 sileo - Systemair

 

 

 

 

 

 

 

 

 

 

 

 

 

RS

A

B

C

D

E

F

G

H

I

J

K

L

60-35

717

402

640

390

620

370

598

348

128

145

490

524

RFA
DXF
GFL 60-35 Counter flange - Systemair
Art. no.: 2709
GFL 60-35 Counter flange .
Motor protect. switch S-DT 16 - Systemair
Art. no.: 161206
Motor protect. switch S-DT 16 .
Motor protect. switch S-DT 16E - Systemair
Art. no.: 161207
Motor protect. switch S-DT 16E .
REV-5POL/07-7,5kW R/Y - Systemair
Art. no.: 33980
REV-5POL/07-7,5kW R/Y .
RTRD 2 Speed Cont. Systemair - Systemair
Art. no.: 5941
RTRD 2 Speed Cont. Systemair .
RTRDU 2 Speed contr. Systemair - Systemair
Art. no.: 5945
RTRDU 2 Speed contr. Systemair .
STDT 16E Motor Protection - Systemair
Art. no.: 5153
STDT 16E Motor Protection .
CO2RT-R-D Transmitter - Systemair
Art. no.: 6993
CO2RT-R-D Transmitter .
DTV500A - Systemair
Art. no.: 96807
DTV500A .
HR1 Room Humidistat - Systemair
Art. no.: 215150
HR1 Room Humidistat .
Presence detector/IR24-P - Systemair
Art. no.: 6995
Presence detector/IR24-P .
RT 0-30 Room Thermostat - Systemair
Art. no.: 5151
RT 0-30 Room Thermostat .
Safety switch 3-pole grey - Systemair
Art. no.: 210680
Safety switch 3-pole grey .
T 120 Timer - Systemair
Art. no.: 5165
T 120 Timer .
DS 60-35 Flexible connection - Systemair
Art. no.: 1549
DS 60-35 Flexible connection .
DXRE 60-35-3-2,5 Duct cooler - Systemair
Art. no.: 7956
DXRE 60-35-3-2,5 Duct cooler .
FFK 60-35 Filter cassette rect - Systemair
Art. no.: 1761
FFK 60-35 Filter cassette rect .
LDR 60-35 Silencer - Systemair
Art. no.: 5073
LDR 60-35 Silencer .
PGK 60-35-3-2,0 Duct cooler - Systemair
Art. no.: 6612
PGK 60-35-3-2,0 Duct cooler .
RB 60-35/27-2 400V/3 Duct heat - Systemair
Art. no.: 9643
RB 60-35/27-2 400V/3 Duct heat .
RB 60-35/45-3 400V/3 Duct heat - Systemair
Art. no.: 9644
RB 60-35/45-3 400V/3 Duct heat .
RBM 60-35/27 400V/3 Duct heate - Systemair
Art. no.: 5454
RBM 60-35/27 400V/3 Duct heate .
VBR 60-35-2 Water heating batt - Systemair
Art. no.: 5467
VBR 60-35-2 Water heating batt .
VBR 60-35-4 Water heating batt - Systemair
Art. no.: 5475
VBR 60-35-4 Water heating batt .
Room hygrostat HR-S - Systemair
Art. no.: 286251
Room hygrostat HR-S .