Art. no.: 9844
Water-heating battery for heating air in ventilation systems with circular ducts. Aluzinc-coated casing, heat transmission element with copper tubes and aluminium fins. Removable cover for cleaning the unit.
The water-heating battery can be installed in a horizontal or a vertical duct with optional direction of airflow.
Max operating temperature 150 °C
Max operating pressure 1,6 MPa (16Bar)
3-rows battery
Dimensions and weights | ||
---|---|---|
Duct dimension; Circular, inlet | 315 | mm |
Duct dimension; Circular, outlet | 315 | mm |
Weight | 13.3 | kg |
Others | ||
---|---|---|
Duct cooler/heater | Heater coil, water | |
Duct connection type | Circular |
Air flow (m3/s) |
Pressure drop (Pa) |
ΔT air at T water 60/40, ˚C |
Water flow rate (l/s) |
Water speed (m/s) |
Pressure drop (kPa) |
Power (kW) |
ΔT air at T water 90/70, ˚C |
Water flow rate (l/s) |
Water speed (m/s) |
Pressure drop (kPa) |
Power (kW) |
Inlet air temp 0˚C |
VBC 100-3 | VBC 125-3 | VBC 160-3 | VBC 200-3 | VBC 250-3 | VBC 315-3 | VBC 400-3 |
0,04 |
0,06 |
0,1 |
0,15 |
0,25 |
0,39 |
0,63 |
39 |
17,2 |
41 |
29 |
31,2 |
35 |
36,3 |
25,9 |
33,4 |
29,3 |
30,7 |
30,5 |
30,2 |
30,3 |
0,02 |
0,03 |
0,05 |
0,07 |
0,12 |
0,19 |
0,3 |
0,24 |
0,47 |
0,68 |
0,54 |
0,59 |
0,69 |
0,74 |
0,85 |
5,33 |
11 |
5,36 |
6,23 |
8,28 |
10,10 |
1,35 |
2,6 |
3,8 |
6 |
9,93 |
15,3 |
24,74 |
47,4 |
56,2 |
49,7 |
52,1 |
51,6 |
51 |
50,8 |
0,03 |
0,05 |
0,08 |
0,13 |
0,21 |
0,32 |
0,51 |
0,45 |
0,8 |
1,17 |
0,92 |
1,02 |
1,17 |
1,26 |
2,65 |
14 |
29,5 |
14,1 |
16,2 |
21,4 |
26,1 |
2,46 |
4,38 |
6,46 |
10,17 |
16,8 |
25,87 |
41,6 |
ØD | B | H | Ødy | F | G | K | L |
315 |
557 |
504 |
22 |
400 |
40 |
276 |
356 |