Manual five-step transformer (with motor protection) for RVK 315Y4, EX 140A-2,

EX 140A-4,

EX 180A-4,

KTEX, DKEX and DVEX fans.

An integral thermistor releasing unit type U-EK230E with ATEX-approval can be used for the temperature monitoring of motors in explosion protected range. A three-phase transformer which controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted manually, using the control knob on the front of the unit. An integral motor protection device is included which cuts the supply voltage to the fan if the thermistor motor protection triggs. The unit is reset by turning the knob to “0” for 1 minute. Input terminals for room thermostat RT cut supply voltage to the fan when the circuit is broken.

NB. The transformer can not be placed in the EX zone.

Технически параметри

Номинални данни
Напрежение (номинално) 400 V
Честота 50; 60 Hz
Фази 3~
Входящ ток 4 A
Защита/Класификация
Клас на корпуса IP21
Температура на околната среда и въздуховода
Позволена температура на околната среда max 40 °C
Размери и тегла
Тегло 11,2 kg
Images Dimensions - R-DK4 KT Transformer (302568) - Systemair
W x H x D

 

270

323

163

[mm]