CO2 and Temperature controller 100-240VAC, 50/60 Hz
Артикулен номер: 24808
• Simple to install, connect and set up
• 50/60HZ mains option
• Can be used with all 220V single phase and 380V three phase EC fans
• Built in sensors
• Conforms to CE standards EN 60730-1, EN 61000-6-3, EN 61000-6-1
• Demand control made simple
The controller compares room temperature with an adjustable set point (knob) and regulates a 0..10 V proportional integral INTERNAL 1 SIGNAL in direct or reverse action based on jumper JP1 setting:
JP1 closed 1-2 = heating (reverse action)
JP1 closed 2-3 = cooling (direct action)
The controller compares also CO2 with an adjustable set point (SW3) and regulates a 0..10 V proportional INTERNAL 2 SIGNAL in direct action.
The output signal applied to a ventilator is the maximum between INTERNAL 1 SIGNAL and INTERNAL 2 SIGNAL.
The range for temperature knob set point is from 5 to 30°C
Номинални данни | ||
---|---|---|
Номинално напрежение | 85 до 265 | V |
Честота | 50; 60 | Hz |
Входна мощност | 2 | W |
Температура | -20 до 50 | °C |
Температурна зададена стойност | 5 до 30 | °C |
Защита/Класификация | ||
---|---|---|
Клас на корпуса | IP30 |
Размери и тегла | ||
---|---|---|
Тегло | 0,147 | kg |
Други | ||
---|---|---|
Измерване на CO2 | 0 до 2.000 | ppm |